Phenix Technologies AC Dialectric Test Set, 600S SERIES
Regulation Section
Model6TS30-20,
Serial Number 94-420
Year of Manufacture 1995
Input Voltage 480V, 50 Amp, 60 Hz, 1 Phase
Output Voltage 480V, 50 Amp, 60 Hz, 1 Phase, 20 KVA
Phenix Technologies Transformer
Model6TS30-20,
Serial Number 94-420
Year of Manufacture 1995
Diagram GO-1470
Untanking Core and Coils 457 lbs
Tank Fittings 114 lbs
Oil capacity 32 Gals
HV Connections 30 KV, 667 Amps, 8.9% impedence
TECHNICAL SPECIFICATIONS
Input:480 volts, 60 Hz, single phase, 20 kVA, 50 amperes
Output Rating :30 kilovolts, .667 amperes
Duty Cycle:1 hour ON/1 hour OFF, 20 kVA.
Continuous at 14 kVA.For overload duty cycles see Figure A.
Type of Cooling:Uncirculated oil
Distortion:Less than 5 percent
Partial Discharge:Less than 10 PC at 30 kV
Impedance :Less than 15 percent at rated current.
Operating Ambient Temperature
Indoor:Output Termination
High Voltage bushing with toroid.
Metering
Output Voltmeter:4.5" (114 mm) analog type, accuracy 2% of full scale.
Range of 0 to 6/12/30 kV.
Output Currentmeter:4.5" (114 mm) analog type, accuracy 3% of full scale.
Range of 0 to 750 milliamperes.:Sizes and Weights
Control Section: 20" W x 18" L x 6" H; 22 lbs.
Regulator Section: 22 1/4" W x 24 1/4" L x 29" H; 220 lbs.
High Voltage Section: 24 1/2" W x 27 1/2" L x 28 1/2" H, plus bushing height of
13 1/2", 810 lbs.
Operating Manual on File